Internal Leak Tester
-
Measures leak flow rates from 0 to 400 mL/min at up to 2.5 bar gauge maximum test pressure. Working fluid: 50/50 water/glycol mixture.
-
Two Coriolis flow meters are used for accurate flow rate measurement — one for high values and one for low leakage rates (<30 mL/min).
-
Software-controlled solenoid valves select module ports for testing based on the test script.
-
In automatic mode, the test sequence runs autonomously, without operator intervention, unless an error condition is detected.
-
Includes remote diagnostics and programming interface.
Performs internal leak testing of multi-chamber cooling distribution modules. Supports both manual and automatic testing modes.