Graphtec GLT400
Embedded midi Logger for automation cabinets – enables communication with PLC via Modbus/TCO protocol; supports remote monitoring and controlling by WEB Server/FTP Server
In stock
Configuration
Useful functions of GLT400
Mount or embedded into the system and remote monitoring by PC.
Enable to transfer the data to the PLC. It can be used as additional I/Os.
Connect as a remote terminal unit of GL840
Various kinds of input type (Analog signal input)
Temperature: -20 ℃ up to 60 ℃
Thermocouple:K, J, E, T, R, S, B, N, C (WRe5-26)RTD (Resistance Temperature Detector): Pt100, JPt100,Pt1000 (IEC751)
Humidity
0 to 100 % RH - using the humidity sensor
4-20mA Current
using optional shunt resistance 250Ω
Digital I/O port available (Requires option B-513)
- Logic/Pulse inputs (4 channels)
- Pulse mode: Instant/Counts/Revolutions
- Signal input for external trigger or external sampling.
- Alarm output (4ch) When the input value exceeded the threshold level, output the alarm.
- Output format: Open collector output (5 V, pull-up resistance 10KΩ).
Expandable up to 200 channels
Save data in the Flash Memory
- Built-in 4GB Flash Memory
- SD Card Slot
- Support SDHC memory card
- Up to 32GB
*Maximum capture capacity in one file is 2GB
Specifications & Accessories
(*1) Possible to save up to 2GByte for one file.
(*2) Main unit, Anlalog terminal and Terminal base unit are installed. AC adapter is not included in dimensions and weight specification.
| Item | Description | |
|---|---|---|
| Number of analog terminal units | Maximum 10 units (200CH) | |
| How to connect Analog Terminal Unit | Direct-connect or connect with the extension terminal connection cable (sold separately) between the GLT400 and terminal unit, or between terminal units. Cables are 50cm or 2m length. | |
| Memory devices | Memory capacity (*1) | Internal memory (MEM) : approx. 4GB |
| SD CARD slot: 1 (Compatible with SDHC, up to approx. 32GB memory available. The memory format only supports FAT/FAT32. ) |
||
| Memory contents | Setup conditions, Measured data | |
| PC Software | Standard Accessories (GLT400 Setting App, GL-Connection) | |
| PC I/F | Types | Ethernet (10BASE-T/100BASE-TX), USB 2.0, Wireless LAN (Option) |
| Functions | Setup and control of the GLT400 from PC, Data transfer to the PC, Connect to network as a remote terminal unit of GL840 |
|
| Ethernet functions | Web server functions, FTP server function, FTP client function, NTP client function, DHCP client function, Modbus/TCP Protocol |
|
| USB functions | USB drive mode:Transfer and delete the captured files in the internal memory or SD CARD | |
| Operating Environment | -20 to 60°C (Temperatures vary by analog terminal, AC adapter: 0 to 45°C) 5 to 85%R.H. (non condensed) (When using the USB PD as the power supply, the spec. is based on power supply requirements.) |
|
| Power source | AC Adapter | 100 to 240 V AC, 50/60 Hz |
| DC power | 8.5 to 24V DC (maximum 26.4V) (DC drive cable (option B-514) is required)) | |
| USB PD | USB PD compatible, external USB PD compatible battery (USB Power Delivery Revision 2.0 later) | |
| External dimensions (approx.) [W×D×H] (*2) | Input terminal (B-564) or Screwless terminal (B-564SL) is attached: 187.5 × 183 × 65.5 mm (excluding protrusions) | |
| Input terminal (B-565): 187.5×183×65.5mm (excluding protrusions) | ||
| Weight (approx.) (*2) | 1120 g (In case input terminal (B-565) is attached: Differ according to terminal type) | |
| Others | Vibration -tested condition: Automobile parts Type 1 Class A equivalent | |
(*2) Main unit, Anlalog terminal and Terminal base unit are installed. AC adapter is not included in dimensions and weight specification.
| Item | Standard terminal (B-564) |
Screwless terminal (B-564SL) |
Withstand high-voltage high-precision terminal (B-565) | |
|---|---|---|---|---|
| Number of analog channels | 20ch | 20ch | 20ch | |
| Input terminal type | M3 screw type terminal | Screwless terminal | M3 screw type terminal | |
| Input method | Photo MOS relay scanning system. All channels isolated balanced input * Terminal b to be used to connect the Resistance bulb is shorted within all channels. |
|||
| Sampling speed | 10msec to 1 hour depending on configuration | |||
| Measurement range | Voltage | 20・50・100・200・500mV, 1・2・5・10・20・50・100V, 1-5V F.S. (Full Scale) | ||
| Temperature | Thermocouple: K・J・E・T・R・S・B・N・C (WRe5-26) RTD (Resistance Temperature Detector): Pt100・JPt100・Pt1000 (IEC751) Temperature range: 100 ° C, 500 ° C, 2000 ° C (Fahrenheit: 150 ° F, 750 ° F, 3000 ° F) |
|||
| Humidity | 0 to 100 % (using the humidity sensor (option B-530)) | |||
| A/D converter | Sigma-Delta type, Resolution: 16-bit (effective resolution: 1/40000 of the +/- range) | |||
| Maximum input voltage |
Between (+) / (-) terminal | 20 mV to 2 V range: 60 Vp-p, 5 V to 100 V range: 110 Vp-p | ||
| Channels ((-) / (-)) | 60Vp-p | 600Vp-p | ||
| Channel / GND | 60Vp-p | 300Vp-p | ||
| Filter (moving average basis) | Off, 2, 5, 10, 20, 40 | |||
| Operating environment | -20 to 60 ºC (5 to 85%R.H.) | 0 to 45℃ (5 to 85%R.H.) | ||
| Item | Model Number | Description |
|---|---|---|
| Standard Terminal | B-564 | Analog Input terminal |
| Screwless terminal | B-564SL | Analog Input terminal |
| Withstand high-voltage high-precision terminal | B-565 | Analog Input terminal |
| Base unit for input terminal | B-566 | Base unit for input terminal (B-564, B-564SL or B-565) |
| Connection cable for extension terminal (50 cm) |
B-567-05 | Cable to connect GLT400 and B-566, 50 cm long |
| Connection cable for extension terminal (2 m) |
B-567-20 | Cable to connect GLT400 and B-566, 2 m long |
| Wireless LAN unit | B-568 | |
| Bracket for DIN rail (extension terminal) | B-540 | |
| Terminal base cover | B-588 | * Compatible with all the terminal, except using with shunt resistor. |
| Models | |
| GLT 400 | Livrare din stoc In stock |
| Documents | |
| Specifications | Download - Data Logger midi Graphtec GLT400 DataSheet |
Industrial software
We provide industrial data acquisition and control software, custom made for customer's needs
MoreDesign and engineering
Our company provides turn-key solutions, including design of complex industrial equipment ...
MoreATEX authorization
Our company is certified by INSEMEX for engineering, installation, maintenance and inspection of Ex area installations ...
View certificate